Download PDF of this page  Print this page
Home » AC/DC Formulas

AC/DC Formulas

To Find

Direct Current

AC / 1phase
115v or 120v

AC / 1phase
208,230, or 240v

AC 3 phase
All Voltages

Amps when
Horsepower is Known

HP x 746
E x Eff

HP x 746
E x Eff X PF

HP x 746
E x Eff x PF

HP x 746
1.73 x E x Eff x PF

Amps when
Kilowatts is known

kW x 1000
E

kW x 1000
E x PF

kW x 1000
E x PF

kW x 1000
1.73 x E x PF

Amps when
kVA is known

 

kVA x 1000
E

kVA x 1000
E

kVA x 1000
1.73 x E

Kilowatts

I x E
1000

I x E x PF
1000

I x E x PF
1000

I x E x 1.73 PF
1000

Kilovolt-Amps

 

I x E
1000

I x E
1000

I x E x 1.73
1000

Horsepower
(output)

I x E x Eff
746

I x E x Eff x PF
746

I x E x Eff x PF
746

I x E x Eff x 1.73 x PF
746


Key:
E = Voltage I = Amps W = Watts
PF = Power Factor Eff = Efficiency HP = Horsepower
Terms and Conditions | Privacy Policy | Site Map